首页> 外文期刊>Cryogenics >Cryogenic system with the sub-cooled liquid nitrogen for cooling HTS power cable
【24h】

Cryogenic system with the sub-cooled liquid nitrogen for cooling HTS power cable

机译:具有过冷液氮的低温系统,用于冷却HTS电力电缆

获取原文
获取原文并翻译 | 示例
           

摘要

A 10m long, three-phase AC high-temperature superconducting (HTS) power cable had been fabricated and tested in China August 2003. The sub-cooled liquid nitrogen (LN_2) was used to cool the HTS cable. The sub-cooled LN circulation was built by means of a centrifugal pump through a heat exchanger in the sub-cooler, the three-phase HTS cable cryostats and a LN_2 gas-liquid separator. The LN_2 was cooled down to 65 K by means of decompressing, and the maximum cooling capacity was about 3.3 kW and the amount of consumed LN_2 was about 72 L/h at 1500 A. Cryogenic system design, test and some experimental results would be presented in this paper.
机译:2003年8月在中国制造并测试了一条10m长的三相交流高温超导(HTS)电力电缆。使用过冷的液氮(LN_2)来冷却高温超导电缆。过冷LN循环是通过离心泵通过过冷器中的热交换器,三相HTS电缆低温恒温器和LN_2气液分离器建立的。通过减压将LN_2冷却至65 K,在1500 A下最大冷却能力约为3.3 kW,消耗的LN_2量约为72 L / h。将介绍低温系统的设计,测试和一些实验结果在本文中。