NOVA Chemicals' Corunna Ethylene facility has originally been designed to ride through power failure of short duration. Operation of critical rotating equipments with steam drivers along with auto starts on other key equipment was to allow quick recovery of the plant once power supply re-established. The steam system was designed and has always been operated so that it would be unaffected by a loss of power. Power supply to the site has been proven reliable until the year 2000, where only 1 incident had been recorded over 25 years of operations. Since then, 4 occurrences of power losses have been experienced. On 2 of those 4 events, the steam system was lost on low deaerator level and a third event, which could be considered a near miss. Premature losses of the steam system caused a crash shut down of the site leading to damage on a number of process units. Analyses of the water, steam and condensate systems reveals that excessive losses of water along with the duration of the outage are the key contributor to failure of the steam system. This paper presents the key findings from the incidents analyses. Water conservation, steam shedding and proper coordination of emergency shut down activities consistent with reduced capabilities of water supply to the steam system are also discussed.
机译:Nova Chemicals'Corunna乙烯设施最初设计用于通过持续时间短的电源失效。带有蒸汽驾驶员的临界旋转设备以及自动启动的临界旋转设备是在其他关键设备上启动的是,一旦电源重新建立,就可以快速恢复工厂。设计蒸汽系统并始终操作,以便它不会受到电力损失的影响。该网站的电源已被证明直至2000年,只有1次事件录得超过25年的业务。从那时起,已经遇到了4个出现的功率损失。在这4个事件中的2个活动中,蒸汽系统损失了低脱气器水平和第三次活动,这可能被认为是近小姐。蒸汽系统的过早损失导致坠机关闭现场,导致损坏了许多工艺单位。水,蒸汽和冷凝水系统的分析表明,水的过度损失随着停机的持续时间是蒸汽系统故障的关键因素。本文提出了事件分析的关键结果。还讨论了水系,蒸汽脱落和紧急关闭活动的适当协调一致,与蒸汽体系的供水量降低一致。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号