An investigation of indoor air microbes of two Hong Kong Old Folks Home, one with naturally ventilation and another with mechanically ventilation device, was carried out. Samples of airborne fungi and bacteria were taken from five indoor sites characterized by different human activities. An outdoor sample was also taken for comparison. Airborne microbes were collected by the Reuter Centrifugal Air Sampler (RCS) for viable sampling and Zefon Air-O-Cell (AOC) for non-viable sampling. Dug-borne fungi were also collected by swabbing surfaces of known surface area. In air samples, the fungal counts collected by AOC were higher (10-128 times) than that of RCS. The dominant fungi found in both Homes were similar. In both Homes,Aspergillus spp. had the highest proportion while the abundance of Penicillium spp. and Cladosporium spp. were similar. In the mechanically ventilated Home, the proportion of Cladosporium spp. in dust-borne fungi was much higher than that of Penicllium spp., and was followed by Aspergillus spp.. However, in the naturally ventilated Home, the highest proportion of dust-borne fungi were Pencillius spp. and Aspergillus spp. while the proportion of Cladosporium spp. was the lowest. Both bacterial counts and fungal counts in air in the naturally ventilated Home were higher than that in the mechanically ventilated Home. The lower relative humidity (RH), 56%-69%, in mechanically ventilated Home was probably responsible for lower fungi counts while a high RH, 72%-85%, in the naturally ventilated Home resulted in higher fungal counts. This study suggests that a mechanical ventilation system contribute to better indoor air quality if it can be properly maintained.
机译:进行了两家香港老人家庭室内空气微生物的调查,进行了一种自然通风,另一个用机械通风装置进行。空气中真菌和细菌的样品取自五个室内遗址,其特征在于不同的人类活动。还采用了室外样品进行比较。通过REETER离心式空气取样器(RCS)收集空气传播的微生物,用于可行的采样和Zefon Air-O-Cell(AOC),用于不可行的采样。挖出的真菌也被已知表面积的拭子表面收集。在空气样本中,AOC收集的真菌计数高于RCS的较高(10-128倍)。两个家庭中发现的主要真菌都是相似的。在两个家庭,aspergillus spp。比例比例最高,而Penicillium spp的丰富。和囊孢子spp。是相似的。在机械通风的家中,囊孢子SPP的比例。在粉尘中,真菌远远高于PeNicllium spp。并且随后是aspergillus spp ..但是,在自然通风的家中,粉尘的最高比例是pencillius spp。和曲霉属spp。虽然囊孢子SPP的比例。是最低的。在天然通风的房屋中的空气中的细菌计数和真菌计数高于机械通风的家庭中的空气。较低的相对湿度(RH),56%-69%,在机械通风的家中可能对低清真菌计数可能负责,而高RH,72%-85%,在天然通风的家庭中导致了更高的真菌计数。本研究表明,如果可以正确维护,机械通风系统有助于更好的室内空气质量。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号