It often happens that the noise level in cleanrooms served by Fan Filter Units (FFU's) significantly exceeds the level expected by the design team. Sometimes it even exceeds the level measured in a mock-up cleanroom. This paper examines the reasons for the discrepancy. It shows by theoretical analyses and laboratory test results how some factors affect the noise generated by FFU's and the noise in cleanrooms served by FFU's. These factors include the flow rate and total static pressure of FFU fans, and the amount of sound absorption and number of FFU's in a cleanroom. It also explains the common mistakes with mock-up tests. In the end, the paper recommends several ways to specify FFU noise and provides methods to predict cleanroom noise levels.
机译:它经常发生在风扇过滤器单元(FFU)服务的洁净室中的噪音水平显着超过设计团队预期的水平。有时它甚至超过了在模拟洁净室中测量的水平。本文审查了差异的原因。它通过理论分析和实验室测试结果显示了一些因素影响FFU产生的噪音以及FFU服务的洁净室中的噪音。这些因素包括FFU风扇的流速和总静态压力,以及洁净室内的吸音和FFU的数量。它还解释了模拟测试的常见错误。最终,本文建议使用多种方法来指定FFU噪声并提供预测洁净室噪声水平的方法。