首页> 外文会议>IEEE Holm Conference on Electrical Contacts >Load tap changers: investigations of contacts, contact wear and contact coking
【24h】

Load tap changers: investigations of contacts, contact wear and contact coking

机译:载荷抽头转换器:接触的调查,接触磨损和联系焦化

获取原文

摘要

The Electrical Power Research Institute (EPRI) and BC Hydro (British Columbia, Canada) sponsored a project on improving the maintenance of "on-load tap changers" (LTC). The investigation of contacts focused on stationary reversing switch assemblies (Part 1) and diverter switch contacts (Part 2). For the study of reversing switch assemblies BC Hydro provided an LTC for an in-house "case study" and the actual study lasted about nine months. The objective of this study was the evaluation of stationary reversing switch assemblies and their performance under different current loadings. Resistance, load and operating temperatures were investigated. This work compared the performance of three assemblies, two were new and one was old. The new reversing switch assemblies were made of either copper or of silver alloy (and silver-plated components), while the third, used brass assembly came with the load tap- changer (Part 1). Powertech Labs Inc. conducted in cooperation with BC Hydro, among other investigations, the study of diverter switch contacts of an LTC ("Kent" case study) at one of the utility's substations. This study lasted for nearly one year and addressed transformer oil chemistry, gas evolution and contact performance under conditions of accelerated switch operations (reported elsewhere). In addition various LTC contacts from several substations were assessed. These investigations emphasize the importance of quality control and quality assurance, especially for arcing contacts of the copper infused tungsten type (Part 2).
机译:电力研究所(EPRI)和BC Hydro(不列颠哥伦比亚省,加拿大)赞助了一个改善“载有载龙头”(LTC)的维护的项目。对静止逆转开关组件(第1部分)和转向器开关触点(第2部分)的触点的研究。对于逆转开关组件的研究,BC Hydro为内部的“案例研究”提供了LTC,实际研究持续了大约九个月。本研究的目的是评估静止逆转开关组件及其在不同电流载荷下的性能。研究了抗性,负荷和操作温度。这项工作比较了三个装配的性能,两个是新的,一个是老。新的倒车开关组件由铜或银合金(和镀银组件)制成,而第三种二手黄铜组件随装有载波分接头(第1部分)。 Powertech Labs Inc.与BC Hydro合作,除其他调查中,对LTC的DVERTER切换触点(“肯特”案例研究)的转向界面进行了研究。本研究持续了近一年,并解决了变压器油化学,气体进化和接触性能在加速开关操作条件下(在其他地方报告)。此外,评估来自多个变电站的各种LTC触点。这些调查强调了质量控制和质量保证的重要性,特别是对于铜注入钨型的电弧接触(第2部分)。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号