Load tap changers: investigations of contacts, contact wear and contact coking

机译:负载分接开关:触点,触点磨损和触点焦化的调查

获取原文

摘要

The Electrical Power Research Institute (EPRI) and BC Hydro (British Columbia, Canada) sponsored a project on improving the maintenance of "on-load tap changers" (LTC). The investigation of contacts focused on stationary reversing switch assemblies (Part 1) and diverter switch contacts (Part 2). For the study of reversing switch assemblies BC Hydro provided an LTC for an in-house "case study" and the actual study lasted about nine months. The objective of this study was the evaluation of stationary reversing switch assemblies and their performance under different current loadings. Resistance, load and operating temperatures were investigated. This work compared the performance of three assemblies, two were new and one was old. The new reversing switch assemblies were made of either copper or of silver alloy (and silver-plated components), while the third, used brass assembly came with the load tap-changer (Part 1). Powertech Labs Inc. conducted in cooperation with BC Hydro, among other investigations, the study of diverter switch contacts of an LTC ("Kent" case study) at one of the utility's substations. This study lasted for nearly one year and addressed transformer oil chemistry, gas evolution and contact performance under conditions of accelerated switch operations (reported elsewhere). In addition various LTC contacts from several substations were assessed. These investigations emphasize the importance of quality control and quality assurance, especially for arcing contacts of the copper infused tungsten type (Part 2).
机译:电力研究所(EPRI)和BC Hydro(加拿大不列颠哥伦比亚省)发起了一个有关改善“有载分接开关”(LTC)维护的项目。对触点的研究主要集中在固定换向开关组件(第1部分)和切换开关触点(第2部分)上。为了研究换向开关组件,BC Hydro提供了一个内部“案例研究”的LTC,实际研究持续了大约9个月。这项研究的目的是评估固定式换向开关组件及其在不同电流负载下的性能。研究了电阻,负载和工作温度。这项工作比较了三个组件的性能,其中两个是新组件,一个是旧组件。新的换向开关组件由铜或银合金(以及镀银的组件)制成,而第三个用过的黄铜组件与有载分接开关一起提供(第1部分)。 Powertech Labs Inc.与BC Hydro合作进行了一项调查,其中之一是在公用事业的一个变电站中对LTC的切换开关触点进行研究(“ Kent”案例研究)。这项研究持续了将近一年,涉及加速开关操作条件下的变压器油化学,气体逸出和接触性能(其他地方报道)。此外,还评估了来自多个变电站的各种LTC触点。这些研究强调了质量控制和质量保证的重要性,特别是对于铜钨注入类型的电弧触头(第2部分)。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号