Development of an efficient static-type ice-storage-device using low concentration aqueous solution - experiments using bare and finned tubes

机译:使用低浓度水溶液的高效静态型冰储物装置的研制 - 使用裸露和翅片管的实验

获取原文

摘要

If aqueous solution with low concentration is used for static-type ice-storage-device, even when the large amount of solution is solidified, the pressure increase can be prevented because of existing of the continuous liquid phase in a solidified layer which opens to an air gap at the top of the vessel. There is also some possibility of augmentation on the melting rate, because hot melt could permeate a mushy region and melt the mush. In the present study, experiments using bare and finned tubes in a test cell have been made for initial concentration of aqueous ethylene glycol ranged from 0% to 2.0% in mass.
机译:如果使用低浓度的水溶液用于静态型冰储存 - 装置,即使当凝固大量溶液时,也可以防止压力增加,因为固化层中的连续液相存在于开口容器顶部的气隙。还有一些可能在熔化率上增加,因为热熔熔化可能渗透糊状区域并熔化糊状物。在本研究中,已经对测试电池中的裸露和翅片管进行实验,用于初始浓度的乙二醇水溶液,范围为0%至2.0%。