【24h】

Tests of Combustion of Aluminum Packing and Trayed Columns

机译:铝包装燃烧和托盘柱的试验

获取原文

摘要

The flammability of structured packing made of thin aluminum sheet (0.2 mm) for use in oxygen service has been investigated by several companies and the results have been published since the first paper was given by Dunbobbin et al. All these previous tests involved small samples of about 100 g. The propagation on such small samples is quite difficult to analyze especially with LOX flowing down, as in actual operating conditions. The results of these tests have been published in STP 1197 Three sets of tests have been performed on larger samples to closely reproduce the operating conditions of cryogenic columns. The first set involved larger packing samples (650 g) above a LOX pool, heated to create a gas flow. The second set involved seven complete columns, 30 cm diameter x 2 m high, containing packing with LOX flowing down. The ignition pack was similar to the first set of samples. The third set involved twelve complete columns, 30 cm diameter x 2 m high, with 20 aluminum trays, in normal working conditions. The ignition cell failed in six tests so only six tests were significant. Results of this investigation performed on large samples were used when preparing the CGA pamphlet G-4.8 published in 1993, which concluded that aluminum structured packing in ASUs introduces no additional risk, compared with aluminum trays.
机译:由薄铝板(0.2 mm)作为在氧服务使用的结构填料的可燃性已经由几家公司研究,结果已经发表由于第一纸张被Dunbobbin等人给出。所有这些以前的测试中所涉及的约100g小样本。在这样小的样品的传播是相当困难与LOX向下流动,如在实际运行条件尤其是分析。这些测试的结果已发表在STP 1197三组的测试已在较大的样本进行密切重现低温列的操作条件。第一组涉及较大的填料样品(650 G)上方的LOX池,加热以产生气流。第二组涉及7个完整的列,直径30厘米×2米高,含填料与LOX向下流动。点火包类似于第一组样品。第三组参与12个完全列,直径30厘米×2米,高,用20个铝盘,在正常的工作条件。在六个试验失败的点火单元所以只有六个测试均显著。大的样品进行本研究的结果在制备CGA小册子G-4.8在1993年出版,其结论在空分铝结构填料没有引入额外的风险,与铝相比,托盘使用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号