The starting performance of 5-60 MW solid-pole salient synchronous motors having 4 or 6 poles is discussed. The rated performance derived by voltage-scaling from reduced-voltage factory tests, is compared against onsite measurements and rated-voltage factory tests. Issues addressed by the paper are the need for: accurate but practical measurement methods, individual focus upon the average and the pulsating torques, stringent test floors procedures (when collecting reduced voltage tests data), reliable voltage scaling factors, correct interpretation of relevant Institute of Electrical and Electronic Engineers guidelines, and finally, the role of the load (inertia) in defining the starting performance of synchronous motors. Shown is that even the best of existing voltage scaling methods do not allow a true estimation of onsite measurements due to the absence of the load (inertia) during reduced voltage factory tests. The electrical measurement method is found to be the most practical and accurate method for the measurement of pulsating torques. A need for clearer IEEE scaling recommendations that also consider the load in addition to voltage effects is corroborated.
机译:讨论了具有4或6极的5-60 MW固态突出同步电动机的起始性能。通过降压厂测试通过电压缩放导出的额定性能,与现场测量和额定电压厂测试进行比较。本文解决的问题是需要:准确但实用的测量方法,个人专注于平均和脉动扭矩,严格的测试地板程序(当收集降低电压测试数据时),可靠的电压缩放因子,正确解释相关研究所电气和电子工程师指南,最后,负载(惯性)在定义同步电机的起始性能方面的作用。表明,即使是现有的电压缩放方法的最佳状态也不允许由于在降低电压厂测试期间没有负载(惯性)而真正估计现场测量。发现电测量方法是测量脉动扭矩的最实用和准确的方法。需要更清晰的IEEE缩放建议,即除了电压效应之外还考虑负载。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号