首页> 外文会议>Electrical electronics insulation conference >Improvements to partial discharge screening test for stator bars and coils
【24h】

Improvements to partial discharge screening test for stator bars and coils

机译:用于定子杆和线圈的局部放电筛选试验的改进

获取原文

摘要

In 1991 and 1992, the authors published the description of a circuit for measuring partial discharge (PD) associated with individual stator bars and coils using a commercial single channel pulse height analyzer together with a sensing system consisting of an 80 pF coupling capacitor terminated in 50 ohms at the instrumentation. The sensing system has a theoretical lower -3 dB point of 40 MHz, while the bandwidth of the instrumentation extends to 100 MHz. The advantage of such a system over measurements at lower frequency (1 MHz) is that the response to external discharges on the end arms is reduced, rendering the system preferentially sensitive to PD in internal voids and delaminations. The purpose of this paper is to describe changes to improve the high frequency response of the circuit and the repeatability of the method.
机译:1991年和1992年,作者公布了使用商业单通道脉冲高度分析仪测量与单个定子杆和线圈相关的局部放电(PD)的电路的描述以及由50的80PF耦合电容组成的传感系统欧姆仪器仪器。传感系统具有40MHz的理论下降-3 dB点,而仪器的带宽延伸至100MHz。这种系统在较低频率(> 1MHz)上的测量的优点是降低了对端臂上的外部放电的响应,使得在内部空隙和分层中优先对PD敏感的系统。本文的目的是描述改善电路的高频响应的变化和方法的可重复性。