Improvements to partial discharge screening test for stator bars and coils

机译:改进了定子棒和线圈的局部放电屏蔽测试

获取原文

摘要

In 1991 and 1992, the authors published the description of a circuit for measuring partial discharge (PD) associated with individual stator bars and coils using a commercial single channel pulse height analyzer together with a sensing system consisting of an 80 pF coupling capacitor terminated in 50 ohms at the instrumentation. The sensing system has a theoretical lower -3 dB point of 40 MHz, while the bandwidth of the instrumentation extends to 100 MHz. The advantage of such a system over measurements at lower frequency (>1 MHz) is that the response to external discharges on the end arms is reduced, rendering the system preferentially sensitive to PD in internal voids and delaminations. The purpose of this paper is to describe changes to improve the high frequency response of the circuit and the repeatability of the method.
机译:在1991年和1992年,作者发表了使用商用单通道脉冲高度分析仪以及由80 pF端接电容组成的传感系统来测量与单个定子条和线圈相关的局部放电(PD)的电路的说明。仪表处的欧姆。感测系统的理论上较低的-3 dB点为40 MHz,而仪器的带宽则扩展到100 MHz。这种系统相对于较低频率(> 1 MHz)的测量的优势在于,减少了对末端臂上外部放电的响应,从而使该系统优先对内部空隙和分层中的PD敏感。本文的目的是描述为改善电路的高频响应而进行的更改以及该方法的可重复性。