首页> 外文会议>IEEE Power Energy Society General Meeting >The Comparative Investigation on Current Differential Criteria Between the One Using Phase Current and the One Using Phase-Phase Current Difference For the Transformer Using Y-delta Connection
【24h】

The Comparative Investigation on Current Differential Criteria Between the One Using Phase Current and the One Using Phase-Phase Current Difference For the Transformer Using Y-delta Connection

机译:使用Y-Delta Connection使用相电流和使用相位电流差的相位电流差的电流差分标准的比较研究

获取原文

摘要

The performance of two types of current differential protection criteria is investigated by quantitative analysis. Among which, one is the criterion based on phase current differential (PD), and the other is implemented based on the phase-phase current differential (PPD). Some manufacturers claim that the zero sequence current is removed when PPD based criterion is applied and the sensitivity of the protection in the event of the earthed fault is lowered. This point of view is challenged in this paper, and the PD based differential criterion is introduced as the reference to investigate the performance of the PPD based criterion. It is proven with the sensitivity analysis that the improvement to the sensitivity arising from the PD comes from the revision of the bias current rather than the differential current.
机译:通过定量分析研究了两种类型的电流差分保护标准的性能。其中,一个是基于相电流差分(PD)的标准,另一个基于相位电流差分(PPD)来实现。一些制造商声称,当PPD基准的标准应用并且在接地故障发生的情况下,保护基于PPD标准时,返除零序电流。在本文中,该观点受到挑战,并引入了PD基于PD基于PPD标准性能的参考。据证明,灵敏度分析,即从PD引起的灵敏度的改善来自偏置电流的修改而不是差分电流。