首页> 外文会议>IEEE Power Energy Society General Meeting >Development of Voltage Sag Metric for Large Meshed Transmission Systems and Stochastic Fault Data Sensitivity Analysis
【24h】

Development of Voltage Sag Metric for Large Meshed Transmission Systems and Stochastic Fault Data Sensitivity Analysis

机译:大型网型传输系统电压张力度量的开发和随机故障数据敏感性分析

获取原文

摘要

This paper describes an approach to determine the impact zone and voltage sag metric for delivery points (DP) in large meshed transmission systems. The metric is to quantify the severity and frequency of voltage sag (VS) experienced at particular DPs. The network model of the system is developed and verified for voltage sag calculation using fault data captured by the power quality (PQ) meters installed across the system. The validated model is used to form the impact zone in terms of the circuit length causing the voltage sag event. Having the impact zones, stochastic fault data is used to create the voltage sag metric. To show the sensitivity of voltage sag metric to different treatment of stochastic fault data, the voltage sag metric is obtained with two sets of data: individual circuit outage frequency and zonal average outage frequency. The approach is implemented on Hydro One Ontario Transmission system. The results are examined to correlate the system behavior with network configuration, voltage level, and proximity to major stations with auto transformers. The results are validated using the data collected over 3 to 5 years by the PQ meters installed in the system. At utility-scale, the approach is used to proactively predict the impact of new planning projects, the retirement of big generation units, and major system reconfiguration on the voltage sag performance of major stations. Additionally, for customers connected on the low voltage (LV) side of transformer stations, the proposed metric can be used to differentiate the impact of transmission system from the events caused by faults on distribution feeders.
机译:本文介绍了一种方法来确定大网状传输系统中的输送点(DP)的冲击区域和电压SAG度量。度量是量化特定DPS在特定DPS经历的电压SAG(VS)的严重性和频率。开发系统的网络模型,并验证了使用通过系统上安装的功率质量(PQ)仪表捕获的故障数据的电压SAG计算。经过验证的模型用于在导致电压SAG事件的电路长度方面形成影响区域。具有冲击区域,随机故障数据用于创建电压SAG度量。为了示出电压SAG度量的灵敏度对随机故障数据的不同处理,用两组数据获得电压SAG度量:单个电路中断频率和区域平均中断频率。该方法是在Hydro One Ontario传输系统上实施的方法。检查结果以将系统行为与网络配置,电压电平和与自动变压器的主要站相关联。使用在系统中安装的PQ仪表以超过3到5年收集的数据进行验证。在公用事业范围内,该方法用于主动预测新规划项目的影响,大一代单位的退休以及主要站点的电压下滑性能的主要系统重新配置。此外,对于连接在变压器站的低压(LV)侧的客户,所提出的指标可用于区分传输系统从分配馈线故障引起的事件的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号