Power system protection upgrade at anclote plant a case study in florida state

机译:死水厂的电力系统保护升级-以佛罗里达州为例

获取原文

摘要

Power system protection coordination is essential for power system reliability and security. This paper focuses on the coordination analysis of the 480VAC system at Anclote plant located in the state of Florida. Due to the obsolete status of the existing trip units associated with the 480VAC power circuit breakers at Anclote plant along with the lack of inventory, in 2016, Duke Energy decided to replace all the varied 480VAC trip units with the Utility Relay Company (URC) AC-PRO® trip units in order to (1) reduce inventory and (2) incorporate a standard trip unit for the 480VAC system. The engineering analysis phase of this project was accomplished by Phasor Engineering and approved by Duke Energy in 2016. Phasor Engineering performed a comprehensive protection coordination study on the 480V trip units of the plant using the following two methods: (1) Sequence of Operation Analysis and (2) Time-Current Curve (TCC) Analysis. The electrical model of the power plant was developed and analyzed using Electrical Transient & Analysis Program (ETAP) software, version 14.1. We plan to present the highlights of this industrial project in two papers. In this paper, a big picture about the problem, case study, different configurations, the characteristics of the employed trip unit, and the adopted strategies to resolve mis-coordination is presented. In the next paper, using the fundamentals given in this paper, we will provide further details about the implementation of this project on all of the 480VAC power circuit breakers at Anclote plant.
机译:电力系统保护协调对于电力系统的可靠性和安全性至关重要。本文着重于佛罗里达州Anclote工厂的480VAC系统的协调分析。由于Anclote工厂与480 VAC电源断路器相关的现有脱扣器的过时状态以及缺乏库存,在2016年,Duke Energy决定用市电继电器公司(URC)AC替换所有变化的480 VAC脱扣器。 -PRO®跳闸单元是为了(1)减少库存和(2)包含用于480VAC系统的标准跳闸单元。该项目的工程分析阶段由Phasor Engineering完成,并于2016年获得Duke Energy的批准。PhasorEngineering使用以下两种方法对电厂480V跳闸单元进行了全面的保护协调研究:(1)操作顺序分析和(2)时间-电流曲线(TCC)分析。使用电气暂态和分析程序(ETAP)软件14.1版开发并分析了电厂的电气模型。我们计划在两篇论文中介绍该工业项目的重点。本文概述了问题,案例研究,不同的配置,所用跳闸单元的特性以及所采用的解决误协调问题的策略。在下一篇论文中,我们将使用本文给出的基础知识,提供有关在Anclote工厂的所有480VAC电源断路器上实施该项目的更多详细信息。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号