Lightning flashes striking a 500 kV transmission lines have been observed using high-speed digital video cameras with the aim of the validations of the electro-geometric model (EGM). Six lightning flashes striking transmission line were observed. In one of the flashes, we observed upward connecting leaders initiated from the transmission line. We estimated the striking distance of the transmission lines from the flashes and compared them with those calculated by the EGM. From the comparison, it was found that the observed-base striking distances were shorter than those calculated by the EGM.
机译:为了验证电几何模型(EGM),已经使用高速数字摄像机观察到闪电击中500 kV传输线。观察到六次闪电击中了传输线。在其中之一的闪烁中,我们观察到了从传输线启动的向上连接的引导线。我们估计了闪光灯产生的撞击线的距离,并将其与EGM计算得出的距离进行了比较。从比较中发现,观察到的基准打击距离比EGM计算的要短。