This paper reports on an examination of the effect of inductive Distributed Flexible AC Transmission System (D-FACTS) devices on the performance of mho ground distance elements. D-FACTS devices supply a distributed solution to avoid transmission bottlenecks, but their operation may contribute in adding more complexity for ground distance elements in cases with fault resistance in the fault path or induced mutual coupling between parallel lines. This work focuses on the influence of these devices on the fault resistance coverage of the ground distance elements. The study analyzes the response of ground distance function in presence of fault resistance for a ground fault and how the power flow direction affects this response. Also, this work explores how D-FACTS impact the mutual coupling degree between the parallel lines and how that may affect the performance of their protection system.
机译:本文报告了对电感式分布式柔性AC传输系统(D-FACTS)设备对mho地面距离元件性能的影响的检查报告。 D-FACTS设备提供了分布式解决方案来避免传输瓶颈,但在故障路径中具有故障电阻或在平行线之间引起互耦的情况下,其操作可能会增加接地距离元件的复杂性。这项工作着眼于这些设备对接地距离元件的故障电阻覆盖率的影响。该研究分析了接地故障时存在接地电阻的接地距离函数的响应,以及潮流方向如何影响该响应。此外,这项工作还探讨了D-FACTS如何影响平行线之间的相互耦合程度,以及如何影响其保护系统的性能。