Westar Lawrence Energy Center Unit 5 in Lawrence, Kansas is a 375 mW unit that utilized a closed loop circulating water system with a wooden cooling tower and three horizontal circulating water pumps to provide cooling water to the condenser. The wooden cooling tower experienced rapid degradation over the past five years of operation. Chlorine was added to the water chemistry to reduce attack of the wooden components, but the chlorine levels in the water caused accelerated corrosion of the pump components and base plates. Circulating water system capacity was reduced due to worn pump components and excessive clearances. Unit load was limited by the lack of adequate circulating water capacity. This paper discusses the pump and motor repairs, design changes performed in parallel with demolition of the wooden cooling tower, and replacement with a new fiberglass tower designed to utilize the existing concrete basin. All of the changes were implemented during an outage in April-May 2009.
机译:Westar Lawrence能源中心单元5在劳伦斯,堪萨斯是一个375 MW装置,利用闭环循环水系统,带有木制冷却塔和三个水平循环水泵,为冷凝器提供冷却水。在过去五年的运营中,木制冷却塔经历了迅速的降解。向水化学中加入氯以减少木质成分的攻击,但水中的氯水平导致泵部件和基板的加速腐蚀。由于泵组件和过度的间隙,循环水系统容量降低。单位负荷受缺乏足够的循环水容量的限制。本文讨论了泵和电机维修,设计变化与木制冷却塔的拆除并联,并用旨在利用现有混凝土盆地的新玻璃纤维塔进行更换。在2009年4月至5月的中断期间实施了所有变化。