FACILITY COOLING FAILURE ANALYSIS OF DIRECT LIQUID COOLING SYSTEM IN DATA CENTERS

机译:数据中心直接液体冷却系统的设施冷却故障分析

获取原文

摘要

This work experimentally studies the impact of facility cooling failure of a direct liquid cooling (DLC) system on the IT equipment (ITE). The facility side of a DLC system removes the heat from a secondary loop-in direct contact with the ITE- and discard it in a chiller loop or ambient. The CPU utilization and coolant set point temperature (SPT) are varied to understand the effect of failure under different operating conditions. The ITE response is studied in terms of chip temperature and power, and fan speed. It was found that failure of the facility cooling system is not hazardous to the IT operation. The rate of change in temperature after failure is low and is sufficient to turn the ITE off safely. This is attributed to the surrounding air in the data center and the thermal mass of the cooling system.
机译:这项工作通过实验研究了直接液体冷却(DLC)系统的设施冷却故障对IT设备(ITE)的影响。 DLC系统的设备侧从与ITE直接接触的次级回路中除去热量,并将其丢弃在冷却器回路或环境中。为了了解不同操作条件下故障的影响,CPU利用率和冷却剂设定点温度(SPT)会有所不同。根据芯片温度和功率以及风扇速度研究了ITE响应。发现设备冷却系统的故障对IT操作没有危害。发生故障后的温度变化率很低,足以安全地关闭ITE。这归因于数据中心中的周围空气和冷却系统的热质量。