MINIMUM AIRFLOW RATES TO DILUTE R290 CONCENTRATIONS ARISING FROM LEAKS IN ROOM AIR CONDITIONERS

机译:最低空气流量,以稀释由于室内空调机泄漏引起的R290浓度

获取原文

摘要

Currently R290 is used to a limited extent in room air conditioners, such as split, portable and window types. The product standard IEC 60335-2-40 currently specifies requirements to limit the charge of flammable refrigerants in such a way that it obstructs the wider use of R290. This is particularly challenging in warm countries where the heat load is greater and thus charge sizes need to be larger for a given room size, inferring higher concentrations in the event of a leak. Relying on the airflow of an indoor unit can be used to dilute a refrigerant leak and thus prevent flammable concentrations forming, despite the charge quantity being substantially greater than that currently permitted in the current standard. Research has been carried out to determine the minimum airflow rate from an air conditioner necessary to achieve sufficient dilution. A numerical model based on entrainment theory was developed and supported by experimentally analysing the behaviour of releases under various conditions with RACS airflow.
机译:当前,R290仅在有限的范围内用于室内空调,例如分体式,便携式和窗户式。产品标准IEC 60335-2-40当前规定了限制易燃制冷剂充入量的要求,以免妨碍R290的更广泛使用。这在热负荷较大的温暖国家尤其具有挑战性,因此对于给定的房间大小,电荷大小需要更大,从而在发生泄漏时推断出更高的浓度。尽管充气量明显大于当前标准中当前允许的数量,但依靠室内机的气流可以减少制冷剂的泄漏,从而防止形成易燃的浓度。已经进行了研究以确定来自空调的最小空气流速,以实现足够的稀释。通过对带有RACS气流的各种条件下的释放行为进行实验分析,开发并支持了基于夹带理论的数值模型。