首页> 外文会议>Brazilian Power Electronics Conference >ACTIVE POWER FILTERING UNDER NON-IDEAL VOLTAGE CONDITIONS USING THE CONSERVATIVE POWER THEORY
【24h】

ACTIVE POWER FILTERING UNDER NON-IDEAL VOLTAGE CONDITIONS USING THE CONSERVATIVE POWER THEORY

机译:使用保守功率理论的非理想电压条件下的有源功率滤波

获取原文

摘要

This paper reviews the capabilities of the conservative power theory (CPT) for active power filtering (APF) and power factor correction, specifically under distorted and asymmetric voltage regime. Both through simulation and experimental verification it is demonstrated how the CPT can selectively neutralize current non-idealities, under harsh voltage conditions. Thus, the experimental results confirm that the CPT framework provides means of achieving Fryze currents, with unity power factor, transporting real power at the minimum line current RMS value.
机译:本文介绍了保守功率理论(CPT)的能力,用于有源电力滤波(APF)和功率因数校正,特别是在扭曲和不对称的电压状态下。通过仿真和实验验证,证明CPT如何在恶劣的电压条件下选择性地中和电流非理想。因此,实验结果证实,CPT框架提供了实现Fryze电流的方法,以统一功率因数,在最小线电流RMS值下运输实际功率。

著录项