Active power filtering under non-ideal voltage conditions using the conservative power theory

机译:使用保守功率理论在非理想电压条件下进行有功功率滤波

获取原文
获取原文并翻译 | 示例

摘要

This paper reviews the capabilities of the conservative power theory (CPT) for active power filtering (APF) and power factor correction, specifically under distorted and asymmetric voltage regime. Both through simulation and experimental verification it is demonstrated how the CPT can selectively neutralize current non-idealities, under harsh voltage conditions. Thus, the experimental results confirm that the CPT framework provides means of achieving Fryze currents, with unity power factor, transporting real power at the minimum line current RMS value.
机译:本文回顾了保守功率理论(CPT)在有源功率滤波(APF)和功率因数校正方面的功能,特别是在失真和非对称电压范围内。通过仿真和实验验证,都证明了CPT如何在苛刻的电压条件下有选择地抵消电流的非理想性。因此,实验结果证实,CPT框架提供了以单位功率因数实现Fryze电流的手段,并以最小线路电流RMS值传输有功功率。