In this paper, the simulation of inter-turn protection for high-voltage (HV) shunt reactors is studied by using Simulink. Expound that when the closing angles of the three-phase circuit breaker are different, the zero-sequence current and zero-sequence voltage will occur in the system. Demonstrated that during such time, the protection criterion of inter-turn protection will be satisfied in some cases, and thus, the false tripping will occur possibly. Finally, some suggestions are given to avoid the false tripping in the inter-turn protection.
机译:本文利用Simulink对高压并联电抗器的匝间保护进行了仿真研究。说明当三相断路器的合闸角度不同时,系统中会出现零序电流和零序电压。证明在此期间,在某些情况下将满足匝间保护的保护标准,因此,可能会发生误跳闸。最后,提出了一些建议,以避免匝间保护中的误跳闸。