Distribution of long duration current impulses in a test house lightning protection system and electrical equipment

机译:测试室防雷系统和电气设备中长时间电流脉冲的分布

获取原文

摘要

Continuing currents, besides the main short duration return strokes, are ones of the basic components of lightning. Open air experiments were conducted to examine the distribution of continuing current components in lightning protection system, supplying cable and electrical installation of the test house equipped with household appliances. The lightning continuing current was physically simulated using a special current generator of long duration impulses. Current impulses were injected from the generator into air termination of the lightning protection system. Measured current distribution in different parts of the test house were compared with results of previous investigations for short duration lightning current impulses. A small increase of efficiency of the lightning protection system was indicated. It means that the ratio between current flowing along the cable to the grounding system of transformer station (remote ground) and current injected into the local ground was 6-8% less compared with the ratio in case of short duration current impulses representing the lightning return stroke.
机译:除主要的短时返回冲程外,持续的电流是雷电的基本组成部分。进行了露天试验,以检查雷电保护系统,供电电缆和装有家用电器的测试室的电气安装中的持续电流组件的分布。使用持续时间长的脉冲的特殊电流发生器对雷电连续电流进行了物理模拟。电流脉冲从发电机注入雷电保护系统的空气终端。将测试室不同部分中测得的电流分布与以前针对短时雷电电流脉冲的调查结果进行了比较。表示防雷系统的效率略有提高。这意味着沿电缆流到变电站的接地系统(远程地面)的电流与注入本地地面的电流之间的比率要比在短时电流脉冲代表雷电返回的情况下的比率少6-8%中风。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号