首页> 外文期刊>Electromagnetic Compatibility, IEEE Transactions on >Current Impulses in the Lightning Protection System of a Test House in Poland
【24h】

Current Impulses in the Lightning Protection System of a Test House in Poland

机译:波兰测试室的防雷系统中的电流脉冲

获取原文
获取原文并翻译 | 示例
           

摘要

The full scale test house was equipped with the lightning protection system and connected to the 15 kV/400 V transformer station. The simulated stroke current was injected into the installation with a current surge generator. Distribution of current in the lightning protection system and connected power supply installation is presented. Measurements were done for several configurations of the LPS, and for current amplitudes ranging from 1 to 10 kA. The results indicated variation with both the amplitude and the shape of the waveforms. The resistance was measured for several groundings individually and for entire grounding system with respect to the surge generator location. Measured waveforms showed frequency-dependent behavior of the circuit. Therefore, in order to improve current simulation accuracy the grounding system impedance should be considered rather than pure resistance. The vertical ground rods of the test house have capacitive impedances, while the long underground cable connected to the grounding system of the transformer has inductive impedance.
机译:全面测试室配备了防雷系统,并连接到15kV / 400V变电站。模拟的冲程电流通过电流浪涌发生器注入设备。介绍了防雷系统和连接的电源设备中的电流分布。对LPS的几种配置以及1至10 kA的电流幅度进行了测量。结果表明随振幅和波形形状的变化。相对于电涌发生器的位置,分别测量了几个接地和整个接地系统的电阻。测得的波形显示了电路的频率相关行为。因此,为了提高电流仿真的准确性,应该考虑接地系统的阻抗而不是纯电阻。测试室的垂直接地棒具有电容性阻抗,而连接到变压器接地系统的长地下电缆则具有电感性阻抗。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号