首页> 外文会议> >Auto Ignition Temperature Test Chamber Fire Investigation
【24h】

Auto Ignition Temperature Test Chamber Fire Investigation

机译:自动点火温度试验箱火灾调查

获取原文

摘要

During routine auto ignition temperature (AIT) testing of a solvent at the NASA White Sands Test Facility (WSTF), a fire breached the test system. The sample being tested was 99 % dodecane (C12). It was exposed to a test atmosphere of 15.7 MPa gas, meeting aviator's breathing oxygen (ABO) specifications (≥99.5 % O_2). During testing, a metal fire occurred, resulting in multiple breaches of the test system. During the event, the chamber pressure transducer mechanically burst, indicating a pressure increase of at least 159 MPa/s. This fire represented the first AIT system breach in 30 years of testing at WSTF. An investigation was undertaken to determine the cause of the breach and to propose countermeasures to prevent future mishaps. A proposed ignition scenario is presented along with an approach for preventing future incidents.
机译:在NASA白沙测试设施(WSTF)进行溶剂的常规自动点火温度(AIT)测试期间,发生了火灾,破坏了测试系统。被测试的样品是99%的十二烷(C12)。它暴露于15.7 MPa的测试气体环境中,符合飞行员的呼吸氧气(ABO)规范(≥99.5%O_2)。在测试过程中,发生了金属火灾,导致多次破坏测试系统。在事件期间,腔室压力传感器会机械破裂,表明压力至少增加159 MPa / s。这场大火是WSTF在30年的测试中首次违反AIT系统。进行了调查以确定违规的原因并提出对策以防止将来发生事故。提出了拟议的点火方案以及防止未来事故的方法。