A new cross-differential protection scheme for parallel transmission lines including UPFC

机译:包括UPFC在内的并行传输线的新型交叉差分保护方案

获取原文

摘要

This paper proposes a new cross-differential protection scheme for a parallel transmission system in the presence of a unified power-flow controller (UPFC) in one line. A cumulative summation technique using three-phase current signals at the sending end is used for fault detection. The faulty phases are then identified by computing the spectral energies of the phasecurrents. The spectral energy of the phase currents is computed by applying a omputationally fast efficient powerful tool known as first Discrete S-Transform (FDST), suitable for analyzing power system signals. The proposed scheme has been extensively tested on different fault conditions with a wide variation in operating parameters. The test results indicate that it can accurately detect and classify the faults with clear discrimination between internal and external faults on a transmission line with a response time of a maximum one cycle from fault inception.
机译:本文提出了一种在统一输电线路控制器(UPFC)存在于一条线路中的情况下,用于并行传输系统的新型交叉差动保护方案。使用在发送端使用三相电流信号的累积求和技术来进行故障检测。然后通过计算相电流的频谱能量来识别故障相。相电流的频谱能量是通过应用一种称为第一离散S变换(FDST)的快速,高效,功能强大的工具来计算的,该工具适用于分析电力系统信号。所提出的方案已经在不同的故障条件下进行了广泛的测试,操作参数变化很大。测试结果表明,它可以准确地检测和分类故障,并且可以清楚地区分传输线上的内部和外部故障,从故障开始到最大响应时间为一个周期。