Improving transient stability of interconnected power systems through HVDC controls

机译:通过HVDC控制提高互联电力系统的瞬态稳定性

获取原文

摘要

AC-DC corridors have been extensively used for bulk power transmission. In many of the cases, the power transfer through the parallel AC lines is restricted due to stability limits. Fast active power modulations of the HVDC link could enhance transient stability of interconnected power systems. This could be achieved by effectively utilizing the available headroom of the HVDC link, especially the transient overloading capability of classic HVDC link. In this paper, control schemes for HVDC power modulations are discussed. The effectiveness of HVDC link power modulations is demonstrated through the improved transient stability of the Pacific AC and DC Interties of North America under critical disturbances. System studies are performed using the detailed dynamic model of the Western Interconnection system.
机译:AC-DC走廊已广泛用于散装电力传输。在许多情况下,由于稳定​​性限制,通过并行交流管线的功率传输受到限制。 HVDC链路的快速有效功率调制可以提高互联电力系统的瞬态稳定性。这可以通过有效利用HVDC链路的可用余量,特别是经典HVDC链路的瞬态过载能力来实现。本文讨论了HVDC功率调制的控制方案。通过在关键干扰下提高了北美的太平洋交流和直流交织的瞬态稳定性,证明了HVDC链路功率调制的有效性。使用Western互连系统的详细动态模型进行系统研究。