首页> 外文会议>IEEE/PES Transmission and Distribution Conference and Exposition >Automatic building of a simulated high impedance fault database
【24h】

Automatic building of a simulated high impedance fault database

机译:自动构建模拟高阻抗故障数据库

获取原文
获取外文期刊封面目录资料

摘要

This paper presents the building steps of a simulated high impedance fault (HIF) database. The simulations were carried out on Alternative Transient Program (ATP) and directed by a Matlab® program. The used HIF model employs two series time-varying resistances controlled by the Transient Analysis of Control Systems (TACS). Actual data obtained by several staged HIFs in different soil types on a distribution system were used to adjust the model. The variables chosen for the different fault schemes were contact surface, fault inception angle, fault location, and load condition. The database is composed by oscillographic data in IEEE-COMTRADE format.
机译:本文介绍了模拟高阻抗故障(HIF)数据库的构建步骤。在替代瞬态程序(ATP)上进行模拟,并由MATLAB ®程序指导。二手HIF模型采用了由控制系统(TAC)的瞬态分析控制的两个串联时变电阻。通过在分配系统上的不同土壤类型中的几种分阶段HIF获得的实际数据用于调整模型。为不同故障方案选择的变量是接触表面,故障成立角,故障位置和负载条件。数据库由IEEE-COMTRADE格式中的示波器数据组成。