Automatic building of a simulated high impedance fault database

机译:自动构建模拟的高阻抗故障数据库

获取原文

摘要

This paper presents the building steps of a simulated high impedance fault (HIF) database. The simulations were carried out on Alternative Transient Program (ATP) and directed by a Matlab® program. The used HIF model employs two series time-varying resistances controlled by the Transient Analysis of Control Systems (TACS). Actual data obtained by several staged HIFs in different soil types on a distribution system were used to adjust the model. The variables chosen for the different fault schemes were contact surface, fault inception angle, fault location, and load condition. The database is composed by oscillographic data in IEEE-COMTRADE format.
机译:本文介绍了模拟高阻抗故障(HIF)数据库的构建步骤。仿真是在替代瞬态程序(ATP)上进行的,并由Matlab ®程序进行控制。所用的HIF模型采用两个串联时变电阻,这些串联时变电阻由控制系统的瞬态分析(TACS)控制。使用分布系统上不同土壤类型中的多个分阶段HIF获得的实际数据来调整模型。为不同的故障方案选择的变量是接触面,故障起始角度,故障位置和负载条件。该数据库由IEEE-COMTRADE格式的示波器数据组成。