首页> 外文会议>International Symposium on Electromagnetic Compatibility >An analysis of the performance of 245 KV circuit breakers applying the radiometric monitoring and the wavelet transform
【24h】

An analysis of the performance of 245 KV circuit breakers applying the radiometric monitoring and the wavelet transform

机译:应用辐射监测和小波变换分析245 KV断路器的性能

获取原文

摘要

This paper presents an analysis of the performance of circuit breakers (CBs) using direct digital sampling and the wavelet transform applied to antenna signals obtained from the arc created during the switching process. Some researches have shown that arcing produces impulsive radio-frequency radiation. Therefore, from timing analysis of the received and recorded impulses, the switching times of circuit breakers can be measured and utilized in order to ensure the safe operation and reliability of these equipments. Results of this analysis are shown for a field measurement realized on 245 kV CBs attached to the capacitor banks at a substation of CEEE-GT in a metropolitan area in southern Brazil.
机译:本文介绍了使用直接数字采样和将小波变换应用于从开关过程中产生的电弧获得的天线信号中得到的断路器(CB)性能的分析。一些研究表明,电弧会产生脉冲式射频辐射。因此,通过对接收和记录的脉冲进行时序分析,可以测量和利用断路器的开关时间,以确保这些设备的安全运行和可靠性。该分析结果显示了在巴西南部都市区CEEE-GT变电站中连接到电容器组的245 kV CB上进行的现场测量。