DYNAMICALLY CONTROLLED LONG DURATION OPERATION OF A HIGHLY ENERGY EFFICIENT CHILLER-LESS DATA CENTER TEST FACILITY

机译:高效节能的无数据中心测试设备的动态控制长时间运行

获取原文

摘要

Data center energy consumption makes up a significant and rapidly growing portion of the national energy use. A large fraction of this energy consumption, in the range of 25%-40%, is used by the data center cooling infrastructure, particularly by the computer room air handlers (CRAH) and by the chiller plant. A joint US Department of Energy and IBM effort investigated the use of warm water server cooling and water side economization to help improve energy efficiency in a volume server by minimizing the use of CRAH and chiller hours with the goal of reducing the ratio of cooling energy to IT energy from the conventional value of approximately 50% to less than 10%. Previous work focusing on system characterization and one day runs found significant energy savings as compared to a traditional chiller based data center. In the work reported in this paper we discuss the development and implementation of a dynamic control approach followed by details and results from a 60+ day run of the data center test facility starting May 11th, 2012. Results from this long term study found the average cooling energy consumption to be 3.5% of the IT energy, which is consistent with previous short one day runs. The implemented control scheme was also able to reliably control the water temperature to within 0.5°C of the set-point under most conditions and could react and stabilize to a new set-point in 30 minutes. The work presented demonstrates the high energy efficiency of a warm water cooled, water-side economized, chiller-less data center over a long sustained period of time and highlights the benefits of energy aware control to help limit cooling energy.
机译:数据中心的能源消耗在全国能源使用中占重要且迅速增长的部分。数据中心制冷基础设施,尤其是计算机房空气处理机(CRAH)和冷水机组使用的能源消耗很大,在25%-40%的范围内。美国能源部和IBM的共同努力研究了温水服务器冷却和水侧节能的使用,通过最大程度地减少CRAH和冷却器小时的使用来帮助提高容量服务器的能源效率,目的是降低冷却能与制冷剂的比例。 IT能耗从常规值的大约50%降低到小于10%。与传统的基于冷却器的数据中心相比,以前专注于系统表征和一日运行的工作可节省大量能源。在本文报告的工作中,我们讨论了动态控制方法的开发和实施,并详细讨论了从2012年5月11日开始的数据中心测试设施运行60天以上的结果。冷却能耗为IT能耗的3.5%,与之前的短短一天运行时间一致。在大多数情况下,已实施的控制方案还能够将水温可靠地控制在设定点的0.5°C以内,并且可以在30分钟内做出反应并稳定至新的设定点。所展示的工作证明了在长期持续的时间内,经热水冷却,在水侧节省能源,无冷却器的数据中心的高能源效率,并着重指出了节能控制可帮助限制冷却能量的好处。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号