首页> 外文会议>IEEE electrical insulation conference >Experience with DC Polarization-Depolarization Measurements on Stator Winding Insulation
【24h】

Experience with DC Polarization-Depolarization Measurements on Stator Winding Insulation

机译:定子绕组绝缘上直流极化-去极化测量的经验

获取原文

摘要

DC insulation resistance (IR) and polarization index (PI) testing is very widely used to assess the condition of the rotor and stator windings in motors and generators. The IR/PI tests are good at identifying contaminated windings; however, such issues as thermal deterioration or abrasion of the insulation due to coil vibration, are not detected by the IR/PI test in modern insulation. The polarization/depolarization current (PDC) test, where the charging current is measured for several minutes and then the test object is grounded and the discharging current is measured for several minutes, may provide more diagnostic information. This paper presents PDC data from a stator as well as individual stator coils and bars and compares it to results from other off-line tests including the low- and high-frequency PD, dissipation factor tip-up, and DC ramp tests. It seems that partial discharge tests are more sensitive to some insulation problems than PDC, however, more results are needed.
机译:直流绝缘电阻(IR)和极化指数(PI)测试非常广泛地用于评估电动机和发电机中转子和定子绕组的状况。 IR / PI测试擅长识别受污染的绕组。但是,现代绝缘中的IR / PI测试未检测到诸如由于线圈振动引起的绝缘热劣化或磨损之类的问题。极化/去极化电流(PDC)测试可以提供更多的诊断信息,在该测试中,先测量几分钟的充电电流,然后将测试对象接地,再测量几分钟的放电电流。本文介绍了来自定子以及各个定子线圈和条的PDC数据,并将其与其他离线测试的结果进行了比较,包括低频和高频PD,耗散因数增加以及DC斜坡测试。似乎局部放电测试比PDC对某些绝缘问题更敏感,但是,需要更多的结果。