摘要

Numerical simulation is key technique for power system dynamics study. It is time-consuming to perform simulations for large-scale interconnected power systems. To improve the computation speed of numerical simulations, external systems can be simplified as loads at boundary buses. The equivalent model of external systems is built with an AutoRegressive model with eXogenous inputs (ARX) from internal systems. To select proper inputs for building equivalent model, a delayed correlation coefficient index (CCI) is adopted in this paper to evaluate the influence of internal quantities on the boundary quantities. Simulations are performed with New England 39-bus model. Two equivalent models built with traditional CCI and the proposed delayed CCI are compared to verify the performance of the proposed equivalent model under faults of different types.
机译:数值模拟是电力系统动力学研究的关键技术。对大型互联电力系统进行模拟是耗时的。为了提高数值模拟的计算速度,外部系统可以简化为边界总线的负载。外部系统的等效模型是用来自内部系统的外源输入(ARX)的自回归模型构建。为了选择用于构建等效模型的正确输入,本文采用了延迟相关系数指数(CCI)以评估内部数量对边界量的影响。使用新英格兰39母线模型进行仿真。将使用传统CCI和提出的延迟CCI构建的两种等效模型,以验证所提出的等效模型的性能下不同类型的故障。