首页> 外文会议>International Conference on System Science and Engineering >An experimental comparison between a microchannel cooler and conventional coolers of a CO_2 air conditioning cycle
【24h】

An experimental comparison between a microchannel cooler and conventional coolers of a CO_2 air conditioning cycle

机译:微通道冷却器与CO_2空调循环常规冷却器之间的实验比较

获取原文

摘要

This paper presented an experimental comparison between a microchannel cooler and two conventional coolers of a CO_2 air conditioning cycle. The conventional coolers and the microchannel cooler were designed to have the same heating capacity; however, the volume of the microchannel cooler is less than conventional coolers. The results indicated that the heat transfer efficiency of the microchannel cooler is higher than those of conventional cooler. However, when cooler pressure was over 100 bar, the microchannel cooler was torn. So, the microchannel cooler should be used at the cooler pressure under 75 bar. In addition, the cycle performed at the evaporative temperature of 9°C, calculating the COP of 6.6 (negligible heat transfer rate of subcooling process). The COP of present study is higher than those obtained from other literature reviews.
机译:本文介绍了微通道冷却器与CO_2空调循环的两个常规冷却器之间的实验比较。传统的冷却器和微通道冷却器设计成具有相同的加热能力;然而,微通道冷却器的体积小于常规冷却器。结果表明,微通道冷却器的传热效率高于传统冷却器的传热效率。然而,当冷却器压力超过100巴时,微通道冷却器被撕裂。因此,微通道冷却器应在75巴下的冷却器压力下使用。另外,在蒸发温度为9℃的循环,计算COP为6.6(过冷过程的可忽略的传热速率)。本研究缔约方会议高于其他文献评论。