首页> 外文会议>International conference on electric technology and civil engineering >Experimental Research on Hydraulic Removing Fouling Heat Exchanger (HRF) (Ⅱ)—Fouling removal characteristics of HRF heat exchanger
【24h】

Experimental Research on Hydraulic Removing Fouling Heat Exchanger (HRF) (Ⅱ)—Fouling removal characteristics of HRF heat exchanger

机译:液压去污热交换器(HRF)(Ⅱ) - HRF热交换器的去除特性的实验研究

获取原文

摘要

In order to investigating the removing fouling characteristics of HRF beat exchanger, the experimental table of flow and heat exchange of urban sewage is established. The experiment results show that the reduction rate of fouling impedance and fouling heat-resistance in a heating periods are both over 70%, when the removing fouling cycle is 10 hours, the cleaning velocity is 5m/s and the cleaning time every time is 1 minute.
机译:为了调查HRF击败交换器的去除结垢特性,建立了城市污水的流量和热交换实验表。实验结果表明,在加热时期的污垢阻抗和污垢耐热性的减少率超过70%,当去除污垢循环为10小时时,清洁速度为5m / s,每次都有1个分钟。