This paper presents the behavior of A992 wide flange steel columns under fire loading. Experimental tests were conducted to investigate the structural-thermal response of steel columns subjected to axial loads and elevated temperatures. Two identical W14X5 3 specimens were tested under (i) non-standard fire loading to determine the axial load capacity at elevated temperature and (ii) standard fire loading to determine the buckling temperature of the axially loaded steel column. For the non-standard fire test (Test I), the monotonically increasing axial load was imposed on the steel column under steady-state heating condition. For the standard fire test (Test II), the steel column carrying the sustained axial load was tested under transient heating condition. The structural-thermal responses of steel columns observed in Test I and Test II were compared including column end rotations, lateral and axial displacements, and steel temperatures. The measured column buckling behaviors were also compared to those obtained by 3D finite element analyses. The results indicated that the end rotations and displacements of the steel column before buckling were affected by the sequence of applied loading. Both Test I and Test II provided the similar prediction of axial load capacity and buckling temperature of the steel columns.
机译:本文介绍了A992宽翼缘钢柱在火荷载下的性能。进行实验测试以研究承受轴向载荷和高温的钢柱的结构热响应。在(i)非标准火荷载下测定两个相同的W14X5 3标本,以确定高温下的轴向荷载能力,以及(ii)标准火荷载下确定轴向荷载的钢柱的屈曲温度。对于非标准耐火试验(试验I),在稳态加热条件下,钢柱承受了单调增加的轴向载荷。对于标准耐火测试(测试II),在瞬态加热条件下对承受持续轴向载荷的钢柱进行了测试。比较了在测试I和测试II中观察到的钢柱的结构热响应,包括柱端旋转,横向和轴向位移以及钢温。还将测得的柱屈曲行为与通过3D有限元分析获得的屈曲行为进行了比较。结果表明,屈曲前钢柱的端部旋转和位移受施加荷载的顺序影响。试验I和试验II均提供了对钢柱轴向载荷能力和屈曲温度的相似预测。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号