Influence of DFIG reactive current injection during a voltage dip on the operation of wind turbine circuit breaker

机译:电压暂降期间DFIG无功电流注入对风力发电机断路器运行的影响

获取原文

摘要

This paper deals with an issue that has not received much attention in literature. The aim of the study is to investigate the influence of doubly fed induction generator (DFIG) reactive current injection during a voltage dip on the operation of a wind turbine circuit breaker. The study is done using a novel hardware-in-the-loop test environment constructed using two real time simulators (dSPACE and RTDS) and commercial protection relay. It is found in this study that the reactive current injection enhances the operation of wind turbine protection since the zero crossing of the circuit breaker currents is achieved earlier. This action may prevent from failed auto reclosing and other safety hazards.
机译:本文所处理的问题在文献中并未引起足够的重视。该研究的目的是研究电压骤降期间双馈感应发电机(DFIG)无功电流注入对风力发电机断路器运行的影响。该研究是通过使用两个实时仿真器(dSPACE和RTDS)和商用保护继电器构建的新型硬件在环测试环境完成的。在这项研究中发现,由于断路器电流的过零是较早实现的,因此无功电流注入可增强风力涡轮机保护的运行。此操作可以防止自动重合闸失败和其他安全隐患。