This paper studies on the influence of grounding electrode shared by UHVDC systems on the environment. According to the design of grounding electrode shared by Yun-Guang UHVDC system and Gui-Guang II HVDC system, the neutral point current of transformers in nearby AC substations are given. The substations with neutral point current which exceeds the limit are listed. The paper also presents the neutral point current of the converter transformer caused by the underground DC current. The corrosion on the reinforcing steel bar inside a hydro power station nearby is analyzed. The influence of the underground DC current on the railway is also discussed.
机译:本文研究了UHVDC系统对环境的接地电极的影响。根据云光UHVDC系统和桂光II HVDC系统共用的接地电极的设计,给出了附近交流变电站的变压器的中性点电流。列出了超过限制的中性点电流的变电站。本文还介绍了由地下直流电流引起的转换器变压器的中性点电流。分析了附近的水力电站内的加强钢条上的腐蚀。还讨论了地下DC电流对铁路的影响。