Tripping of circuit breakers in PV installations due to zero sequence field impedance

机译:由于零序列域阻抗,PV装置中的断路器跳闸

获取原文

摘要

On the roof of a wool processing company a 385 kWp PV installation is installed. When production of the installation is more than 60% of the rated power the circuit breaker trips. Measurements show high THD(U) of phase voltages and variable waveform of both voltage and current. Analysis of the installation showed that a Yy0 transformer is installed introducing a high zero sequence field impedance. Unbalance in the injected current combined with a zero sequence impedance leads to high voltage drops and distorted phase voltages. Measurements also show high RMS values of the current in the neutral conductor. Analyses show that the tripping of the circuit breaker is caused by the measurement method of the device itself. Higher current values are calculated due to multiple zero crossings of both voltage and current. This paper gives the practical measurement results, causes of errors and the solution to the stated problems.
机译:在羊毛加工公司的屋顶上,安装了385 kWp的PV安装。当生产的安装超过额定功率的60%时,断路器跳闸。测量显示电压和电流的相电压和变量波形的高THD(U)。安装分析显示,安装了YY 0 变压器,引入了高零序列阻抗。注入电流中的不平衡与零序阻抗合并导致高压下降和失真的相电压。测量还显示中性导体中电流的高RMS值。分析表明断路器的跳闸是由设备本身的测量方法引起的。由于电压和电流的多个过零点,计算较高电流值。本文给出了实际测量结果,错误的原因和对规定的问题的解决方案。