首页> 外文会议>IEEE Power and Energy Society General Meeting >Field breaker tripping options for generator static excitation systems with AC field circuit breakers - A case study
【24h】

Field breaker tripping options for generator static excitation systems with AC field circuit breakers - A case study

机译:带交流现场断路器的发电机静态励磁系统的现场断路器跳闸选项-案例研究

获取原文

摘要

Short circuit contributions from synchronous generators can persist for several seconds even after the field circuit breaker is opened. Delayed tripping of an AC field circuit breaker can allow faster reduction of generator field current in some circumstances. Faster reduction of generator field current will reduce the energy in a short circuit and consequently reduce the damage caused by the short circuit. This paper describes a case study examining the issues associated with the decision to delay tripping of AC field circuit breakers.
机译:即使在断开现场断路器之后,同步发电机的短路影响仍会持续几秒钟。在某些情况下,交流励磁断路器的延迟跳闸可允许更快地减小发电机励磁电流。发电机励磁电流的更快减小将减少短路时的能量,从而减少由短路引起的损坏。本文描述了一个案例研究,该案例研究了与决定是否延迟交流现场断路器跳闸相关的问题。