In this paper an UPQC (Unified Power Quality Conditioner) with a FLFB (Four-Leg Full-Bridge) inverter used as a Shunt Active Filter is presented. The UPQC works in a three-phase four-wire electrical system in order to compensate for nonlinear and asymmetrical loads, and disturbances in the power supply voltage. For the generation of reference currents for the FLFB the instantaneous power theory in the dqz reference frame is used. The FLFB inverter is modulated using the 3D-SVM (3D-Space Vector Modulation) algorithm to generate the positive, negative and zero sequence voltages required. Finally, PI (Proportional-Integral) controllers are used to adjust the steady state error of the controlled signals in the shunt and series compensator. Simulation results show that when a nonlinear and asymmetrical load is compensated with the proposed UPQC topology and control scheme, unitary power factor, sinusoidal currents and neutral current mitigation can be achieved at the PCC (Point Common Coupling), all of this with constant rms voltage at the load side, independently of the PCC voltage disturbances. As an example, a simulation study is performed in this work obtaining a reduction from 29% to 1.9% in PCC current THD, a reduction from 52.8 (A rms) to 3.4 (A rms) in PCC neutral current, and a 1.3% variation in rms load voltage when a 10% sag occurred in PCC side.
机译:在本文中,提出了一种带有FLFB(四腿全桥)逆变器作为并联有源滤波器的UPQC(统一电能质量调节器)。 UPQC在三相四线电气系统中工作,以补偿非线性和非对称负载以及电源电压中的干扰。为了生成FLFB的参考电流,使用了dqz参考帧中的瞬时功率理论。使用3D-SVM(3D空间矢量调制)算法对FLFB逆变器进行调制,以生成所需的正序,负序和零序电压。最后,PI(比例积分)控制器用于调节并联补偿器和串联补偿器中受控信号的稳态误差。仿真结果表明,当采用提出的UPQC拓扑和控制方案补偿非线性和非对称负载时,可以在PCC(点公共耦合)上实现单位功率因数,正弦电流和中性点电流的减小,而所有这些均以恒定的均方根电压来实现。在负载侧,不受PCC电压干扰的影响。例如,在这项工作中进行了仿真研究,得出PCC电流THD从29%降低到1.9%,PCC中性电流从52.8(A rms)降低到3.4(A rms),变化1.3%当PCC侧发生10%的跌落时,有效负载电压的均方根值。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号