首页> 外文会议>Conference Record of the 2010 IEEE International Symposium on Electrical Insulation >Condition assessment of mixed oil-paper and XLPE insulated cable lines by voltage response method
【24h】

Condition assessment of mixed oil-paper and XLPE insulated cable lines by voltage response method

机译:用电压响应法评估油纸和交联聚乙烯绝缘电缆的状态

获取原文

摘要

The voltage response method is an effective tool to diagnose the condition of the oil-paper insulation. The initial slopes of decay and return voltages are in direct correlation with dielectric processes. Testing of oil-paper insulation with this method the two main deteriorating processes thermal aging and moistening can be investigated separately. The thermal aging of PVC insulation can also be followed by this method. By the newest result of the authors, this method seems a promising tool to solve the diagnostic problem of joint polymeric and oil-paper insulated cable lines. By the newly developed correction method, the aging state of joint (oil-paper and extruded) cable lines can be determined at certain circumstances. Practically, after only one measurement on a mixed cable line the feasible values of voltage response of the both parts can be estimated by the knowledge of the parameters of the sections.
机译:电压响应方法是诊断油纸绝缘状况的有效工具。衰减和返回电压的初始斜率与介电过程直接相关。用这种方法测试油纸绝缘层的两个主要劣化过程,即热老化和湿润,可以分别进行研究。此方法也可以跟踪PVC绝缘材料的热老化。根据作者的最新结果,该方法似乎是解决聚合物和油纸绝缘电缆接头诊断问题的有前途的工具。通过新开发的校正方法,可以在某些情况下确定接头(油纸和挤出)电缆线的老化状态。实际上,仅在混合电缆线上进行一次测量后,即可通过了解这些部分的参数来估算两部分的电压响应的可行值。