This paper took the check of rupturing capacity circuit breaker in petrochemical electric power network for example. It introduced the selection rule of largest short-circuit current which flow through circuit breaker, the principle of short circuit calculation, the equivalent model of external system, the modeling of mathematical model of industrial electric owned power network, and the procedures of short circuit calculations. At same time, the different short-circuit current was calculated which flow through the circuit breaker in both original petrochemical electric power network and the rebuilding one. At last, the simulation example proved that the margin of short-circuit current is less and less or even exceeding with the growth in the loads, increasing in self-power supply and external system in industrial electric power network. The industrial should pay sufficient attention to it.
机译:本文以石化电网中断路器容量的检查为例。介绍了流经断路器的最大短路电流的选择规则,短路计算的原理,外部系统的等效模型,工业电网的数学模型的建模以及短路计算的步骤。 。同时,计算出了不同的短路电流,该短路电流流经原始石化电力网络和重建网络中的断路器。最后通过仿真实例证明,随着电力负荷的增加,工业电网自供电和外部系统的增加,短路电流的裕度越来越小甚至什至超过。工业界应对此给予足够的重视。