首页> 外文会议>SME annual meeting exhibit;CMA's national western mining conference >EFFECT OF AIR VELOCITY ON CONVEYOR BELT FIRE SUPPRESSION SYSTEMS
【24h】

EFFECT OF AIR VELOCITY ON CONVEYOR BELT FIRE SUPPRESSION SYSTEMS

机译:空气流速对输送带防火系统的影响

获取原文

摘要

Four different types of fire suppression systems were evaluated in large-scale fire experiments to study the effect of air velocity on the effectiveness to extinguish conveyor belt fires. The four different types of suppression systems were water sprinkler, deluge type water spray, and two different dry chemical fire suppression systems. The large-scale fire tests were conducted with 72-in-wide fire resistant rubber belt that met the Mine Safety and Health Administration flame resistant requirement specified in Title 30, Code of Federal Regulations, Part 18, section 18.65 (also known as the 2G Flame Test). Each fire suppression system was tested at air velocities of 500-550 feet per minute (fpm) and 1350-1500 fpm. Two tests were conducted at both air velocities for each fire suppression system. Both of the water-based fire suppression systems were able to suppress the fire to the point that a miner could extinguish it with a fire extinguisher. However, the amount of water needed to suppress the fire to the point where a miner could walk up to extinguish any smoldering belting was greater than the current MSHA regulations require. MSHA regulations only require 10 minutes of water supply to the suppression system. In the test set up neither of these systems would have suppressed the fire had the water been turned off to the system after 10 minutes. The dry chemical suppression systems produced mixed results. Dry chemical suppression system A did not suppress the conveyor belt fire at either air velocity. Dry chemical system B suppressed the fire at 500 fpm air velocity, but produced mixed results at the higher air velocity. Details are presented on the large-scale fire test set-up, arrangement of the fire suppression systems, and conclusions regarding the effect of air velocity on fire suppression system design and performance.
机译:在大规模的火灾实验中对四种不同类型的灭火系统进行了评估,以研究空气速度对扑灭传送带火灾的有效性的影响。四种不同类型的灭火系统是洒水器,雨淋式喷水和两种不同的干粉灭火系统。大型防火测试使用72英寸宽的耐火橡胶带进行,该橡胶带符合《联邦法规法规》第30篇第18部分第18.65节(也称为2G)中规定的矿山安全与健康管理局的阻燃要求。火焰测试)。每个灭火系统均以500-550英尺/分钟(fpm)和1350-1500 fpm的风速进行测试。对于每个灭火系统,在两种风速下都进行了两次测试。两种水基灭火系统都能够将火势抑制到矿工可以用灭火器灭火的程度。但是,将火势扑灭至矿工可以向上扑灭任何阴燃带所需的水量大于当前的MSHA法规要求。 MSHA法规仅要求抑制系统供水10分钟。在测试装置中,如果10分钟后将水关闭,则这些系统都无法抑制火灾。干化学抑制系统产生了不同的结果。干粉灭火系统A在任何风速下均未抑制传送带着火。干化学系统B以500 fpm的风速抑制了火灾,但在较高的风速下却产生了混合结果。详细介绍了大型火灾测试的设置,灭火系统的布置以及有关风速对灭火系统设计和性能的影响的结论。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号