首页> 外文会议>Research and Development (SCOReD), 2009 >Improving the lightning protection of O.H.T.L in tropical areas with high resistivity soils through improving the ground systems
【24h】

Improving the lightning protection of O.H.T.L in tropical areas with high resistivity soils through improving the ground systems

机译:通过改善地面系统来改善高电阻土壤热带地区的O.H.T.L防雷

获取原文

摘要

The parallel continuous type of counterpoise wire is the best ground system currently, it is reduce the ground resistance less than 25 ¿ in high resistivity of soil arriving 4450 ¿m with 400 m length. The created ground system types of proposed chem-counterpoise can be used in both homogenous and inhomogeneous soil that have soil resistivity arriving 10000 ¿m. The proposed chem-counterpoise devices will be used to reduce the risk of BFO rate, repeated outage and economic losses.
机译:平行连续地埋线是目前最佳的接地系统,在400 m的土壤到达4450 m的高电阻率中,它的接地电阻降低了25 less长度。拟议中的化学地表的创建的地面系统类型可用于土壤电阻率达到10000μm的均质和非均质土壤中。拟议的化学平衡设备将用于降低BFO率,重复中断和经济损失的风险。