首页> 外文会议>Electric Power and Energy Conversion Systems, 2009. EPECS '09 >Hardware implementation of a hybrid protection scheme for bipolar HVDC line
【24h】

Hardware implementation of a hybrid protection scheme for bipolar HVDC line

机译:双极高压直流输电线路混合保护方案的硬件实现

获取原文

摘要

Implementation of a hybrid protection scheme for bipolar HVDC line with field-programmable gate array (FPGA) is described in this paper. The protection scheme amalgamates a traveling wave protection unit, a boundary protection unit and a lightning unit. Stationary wavelet transform (SWT) and its wavelet modulus maxima are used to remove noise and represent useful traveling wave signal. Boundary protection based on SWT is used jointly with traveling wave protection to distinguish internal faults from external faults. Lightning unit is used to distinguish non-fault transients and to identify the faulty pole. Xilinx XtremeDSP Development Kit-4 is employed for prototyping the relay, with coding done using Xilinx System Generator and AccelDSP.
机译:本文描述了一种采用现场可编程门阵列(FPGA)的双极HVDC线路混合保护方案的实现。该保护方案将行波保护单元,边界保护单元和雷电单元合并在一起。平稳小波变换(SWT)及其小波模极大值用于去除噪声并表示有用的行波信号。基于SWT的边界保护与行波保护结合使用,可将内部故障与外部故障区分开。防雷装置用于区分非故障瞬变和识别故障极。 Xilinx XtremeDSP开发套件-4用于对继电器进行原型设计,并使用Xilinx System Generator和AccelDSP进行编码。