Impact of Vacuum Switch-disconnectorson Reliability of MV distribution networks

机译:空压开关 - 隔离电阻的影响MV分配网络的可靠性

获取原文
获取外文期刊封面目录资料

摘要

Using vacuum technology in 100% of distribution switchgears will increase the number of vacuum interrupters in the network by a factor of 20. Here a statistical analysis is used to evaluate the consequences of a complete substitution of Gas Insulated Switchgear (GIS) by vacuum insultaed switchgears on the reliability of a cable network. Frequency of insulation failures is similar to this due to the vacuum switchgear already used in main distribution. The Average System Interruption Duration is impacted by only 0.03 minutes; to be compared to 0.17 minutes due to insulation failure in the main substation and 20 minutes due to cable failure. With respect to security of operation it is found that the major part of the insulation failures leads to earth fault currents readily interrupted by upstream protection without physical degradation of the equipment. It is concluded that a complete substitution in MV distribution networks by vacuum switch-disconnectors has a negligible impact on reliability and safety.
机译:在100%的分布开关设备中使用真空技术将使网络中的真空中断器的数量增加20倍。这里使用统计分析来评估通过真空insultaed开关柜来评估气体绝缘开关设备(GIS)的完全取代的后果关于电缆网络的可靠性。由于在主要分布中使用的真空开关设备,绝缘故障的频率类似于这。平均系统中断持续时间仅影响0.03分钟;将由于主变电站的绝缘故障和20分钟而将其与0.17分钟进行比较。关于操作的安全性,发现绝缘故障的主要部分导致接地故障电流通过上游保护而不含设备的物理降级。结论是,真空开关隔离器的MV分配网络中的完全取代具有可忽略的可靠性和安全性的影响。