首页> 外文会议>Safety Instrumented Systems for the Process Industry >SIL2/ SIL 3 RATED VIBRONIC POINT LEVEL MEASUREMENT DEVICES FOR OVERFILL PROTECTION
【24h】

SIL2/ SIL 3 RATED VIBRONIC POINT LEVEL MEASUREMENT DEVICES FOR OVERFILL PROTECTION

机译:SIL2 / SIL 3额定过盈点水平测量设备,用于过溢保护

获取原文

摘要

Safety instrumented systems (SIS) that are rated according the Safety Integrity Levels (SIL) are gaining importance in the process industries. In this presentation vibronic point level measurement devices are used in highly reliable overfill protection system will be discussed. Starting from the basics of how these tuning fork system work, the construction principle will be illustrated. With regard to a high functional safety, a focus will be put on the self monitoring capability of vibronic systems and the PFM (pulse frequency modulation) technology that is used for signal transmission from the sensor to the switching amplifier. The combination of these capabilities has led to a SIL2/SIL3 rating of these sensors for overfill protection systems according to the international standard IEC 61508/61511. The probability of failure on demand (PFD) requirements according IEC 61508 fulfilled by these systems are identical to the corresponding American standard ANSI/ISA-S84.01.
机译:根据安全完整性等级(SIL)进行评级的安全仪表系统(SIS)在过程工业中正变得越来越重要。在本演示中,将讨论在高度可靠的溢流保护系统中使用的振动点液位测量设备。从这些音叉系统如何工作的基础开始,将说明其构造原理。关于高功能安全性,重点将放在振动电子系统的自监视功能以及用于从传感器到开关放大器的信号传输的PFM(脉冲频率调制)技术上。这些功能的组合已导致这些传感器根据国际标准IEC 61508/61511达到SIL2 / SIL3等级。这些系统满足的IEC 61508的按需故障概率(PFD)要求与相应的美国标准ANSI / ISA-S84.01相同。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号