The single-phase earth fault is the most common fault type on high voltage transmission line. But the sensitivity of single-phase distance relays can't satisfy the requirement of power system. In order to improve the sensitivity of distance relays to protect the single-phase faults with large earth resistance, one uniform formula is provided to express most of the single-phase distance relays in this paper. More than ten kinds of relays that have been used widely can be expressed by the uniform formula through giving different coefficients. This simplifies the expressions of conventional relays. The uniform formula is helpful to analysis the performance of these relays. It also provides an approach to create new relays with better performance or to lucubrate the correlative principles. Two new relays based on the uniform formula are proposed in this paper. Simulations show that the new relays have better performance than the old ones. At last, the fundamental about the choice of polarization voltage is discussed.
机译:单相接地故障是高压输电线路上最常见的故障类型。但是单相距离继电器的灵敏度不能满足电力系统的要求。为了提高距离继电器的灵敏度,以保护具有较大接地电阻的单相故障,本文给出了统一的公式来表示大多数单相距离继电器。通过给出不同的系数,可以用统一的公式表示十多种已广泛使用的继电器。这简化了常规继电器的表达。统一的公式有助于分析这些继电器的性能。它还提供了一种创建性能更好的新继电器或简化相关原理的方法。本文提出了两种基于统一公式的新型继电器。仿真表明,新继电器的性能要优于旧继电器。最后,讨论了极化电压选择的基本原理。