In selection of the neutral grounding method in a three-phase four-wire 11.4 kV distribution system, it is necessary to take into consideration low voltage rise and induced voltage on telecommunication line in case of ground fault. In this paper, we perform EMTP/ATP simulation to select the optimal neutral grounding method and neutral grounding resistance with consideration to above mentioned conditions. The accuracy of the modeling procedure and simulation result is confirmed through verification test performed on test distribution line. As a result, we found (1) that the 11.4 kV distribution system should be associated with a resistance single grounding method; and (2) that the neutral grounding resistance should be above 20 /spl Omega/.
机译:在三相四线11.4 kV配电系统中选择中性点接地方法时,有必要考虑接地故障时电信线路上的低电压上升和感应电压。在本文中,我们根据上述条件进行EMTP / ATP仿真,以选择最佳的中性点接地方法和中性点接地电阻。通过在测试配电线上进行的验证测试,可以确定建模过程和仿真结果的准确性。结果,我们发现(1)11.4 kV配电系统应与电阻单一接地方法关联; (2)中性点接地电阻应大于20 / spl Omega /。